WILO SE 05/2011
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged
Pump flow
network output SNVT_flow_p nvoFlow
This optional output network variable provides the flow rate determined by
the pump.
Value range
0 - 655.34 m
3
/h (in 0.01 m
3
/h steps). 655.35 m
3
/h is an invalid value.
Transmission
This value is automatically transmitted if it deviates from the value transmitted
last by more than 5% of the value in nroPumpChar.flowMax.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged
Pump speed
network output SNVT_rpm nvoSpeed
This optional output network variable provides the speed of the pump.
Value range
0 – 65535 rpm (in 1 rpm steps).
Transmission
This value is automatically transmitted if it deviates from the value transmitted
last by more than 5% of the value in nroPumpChar.speedMax.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged