English
65
WILO SE 05/2011
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged
Power consumption in kW
network output SNVT_power_kilo nvoPowerkilo
This optional output network variable provides the power consumption of the
pump or, in the event of double pumps, the total power output of the master
and slave.
Value range
0 – 6553.5 kW (in 0.1 kW steps).
Transmission
This value is automatically transmitted if it deviates from the value transmitted
last by more than 10% of the maximum power consumption of the pump.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged
Energy consumption
network output SNVT_elec_kwh nvoEnergyConsum
This optional output network variable provides the energy consumption of the
pump or, in the case of double pumps, the total energy consumption of the
master and slave. The counter is reset to 0 kWh after 65535 kWh.
Value range
0 – 65535 kWh (in 1 kWh steps).
Transmission
This value is transmitted whenever a change is made.
Transmission frequency
The minimum network variable transmission interval can be set by describing
the nciMinOutTm configuration input with a valid clock.
Preset service type: unacknowledged