English
51
WILO SE 05/2011
Maximum status send time
network input config SNVT_elapsed_tm nciMaxStsSendT
This optional input configuration network variable defines a time cycle in which
the object statuses are automatically updated. The status of the node object is
updated in alternation with that of the pump controller object.
Value range:
0d0h0m0s0ms – 0d17h59m59s999ms (in 1 s increments). The value
0d0h0m0s0ms disables the automatic update function.
Initial value: 0d0h0m0s0ms (automatic update function disabled)
SCPT reference: SCPTmaxSendT (22)
Device major version
network output config unsigned short nciDevMajVer
This optional output configuration network variable provides the high byte of
the module version.
SCPT reference: SCPTdevMajVer (165)
Device minor version
network output config unsigned short nciDevMinVer
This optional output configuration network variable provides the low byte of
the module version.
SCPT reference: SCPTdevMinVer (166)
Location label
network input config SNVT_str_asc nciLocation
This optional input configuration network variable can be used to save
information about the installation location of the pump which goes beyond the
information string stored in the Neuron chip, which only consists of 6 Byte.
Value range
Optional NUL-terminated ASCII string of max. 31 bytes length (incl. NUL)
Default value
ASCII string which only consists of NUL (“\0”)
SCPT reference: SCPT_location (17)