en
Commissioning
72
WILO SE 2019-07
Fig. 45:
Menu 5.59
Menu no.
5.59
Description
Collective fault signal (SSM) function
Value range
fall, raise
Factory setting
raise
Explanation
“fall”: The relay drops out. This function can be used to
monitor the mains voltage supply.
“raise”: The relay picks up.
Fig. 46:
Menu 5.60
Menu no.
5.60
Description
Pump cycling
Value range
on, off
Factory setting
on
Fig. 47:
Menu 5.61
Menu no.
5.61 (Control ECe-Booster only)
Description
Zero-flow test
Value range
on, off
Factory setting
on
Fig. 48:
Menu 5.62
Menu no.
5.62
Description
Dry-running protection: Switch-off time delay
Value range
0 … 180 s
Factory setting
15 s
Fig. 49:
Menu 5.63
Menu no.
5.63
Description
Dry-running protection: Reactivation time delay
Value range
0 … 1800 s
Factory setting
10 s
Fig. 50:
Menu 5.68
Menu no.
5.68 (Control EC-Booster only)
Description
Mains connection rotating field monitoring On/Off
Value range
on, off
Factory setting
on
NOTICE! Switch off during alternating current connection!
Fig. 51:
Menu 5.69
Menu no.
5.69 (Control EC-Booster only)
Description
Motor current monitoring On/Off
Value range
on, off
Factory setting
on
NOTICE! Switch off during alternating current connection!
Содержание Control EC-Booster
Страница 2: ......
Страница 46: ...de Anhang 46 WILO SE 2019 07 Legende R nur Lesezugriff RW Lese und Schreibzugriff ...
Страница 434: ...hr Dodatak 434 WILO SE 2019 07 Legenda R samo pristup za čitanje RW pristup za čitanje i pisanje ...
Страница 606: ...nl Bijlage 606 WILO SE 2019 07 Legenda R alleen leestoegang RW lees en schrijftoegang ...
Страница 692: ...pl Załącznik 692 WILO SE 2019 07 Legenda R tylko dostęp odczytu RW dostęp odczytu i zapisu ...
Страница 736: ...pt Anexo 736 WILO SE 2019 07 Legenda R só para acesso de leitura RW acesso de leitura e escrita ...
Страница 1208: ......
Страница 1209: ......
Страница 1210: ......