WILO SE 2019-07
Holding register
(Protocol)
Name
Data type
Scale & unit
Elements
Access*
Added
6. n(TR)
7. n(TP)
8. n(TA)
9. n-c
10. fill
11. empty/drain
12. FTS
13. cleans/day
14. cleans/
month
40026
(25)
Current value
INT16
0.1 bar
0.1 m
0.1 K
0.1 °C
1 cm
1 min
0.1 h
0.1 psi
R
31.000
40041
(40)
Pump 1 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40042
(41)
Pump 2 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40043
(42)
Pump 3 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40062
(61)
Switch box state
BITMAP
0: SBM
1: SSM
R
31.000
40139 - 40140
(138-139)
Error state
BITMAP32
0: Sensor error
1: P max
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6
Alarm
11: -
12: -
13: Frost
14: Battery Low
15: High water
16: Priority off
17: Redundancy
18: Plausibility
19: Slave
communication
20: Net supply
21: Leakage
R
31.000
40141
(140)
Acknowledge
BOOL
W
31.000
40142
(141)
Alarm history index
UINT16
RW
31.000
40143
(142)
Alarm history error
code
UINT16
0.1
R
31.000
Legenda
* R = samo za pristup za čitanje, RW = pristup za čitanje i upisivanje
Содержание Control EC-Booster
Страница 2: ......
Страница 46: ...de Anhang 46 WILO SE 2019 07 Legende R nur Lesezugriff RW Lese und Schreibzugriff ...
Страница 434: ...hr Dodatak 434 WILO SE 2019 07 Legenda R samo pristup za čitanje RW pristup za čitanje i pisanje ...
Страница 606: ...nl Bijlage 606 WILO SE 2019 07 Legenda R alleen leestoegang RW lees en schrijftoegang ...
Страница 692: ...pl Załącznik 692 WILO SE 2019 07 Legenda R tylko dostęp odczytu RW dostęp odczytu i zapisu ...
Страница 736: ...pt Anexo 736 WILO SE 2019 07 Legenda R só para acesso de leitura RW acesso de leitura e escrita ...
Страница 1208: ......
Страница 1209: ......
Страница 1210: ......