Прилог
mk
Упатство за вградување и работа Wilo-Control EC/ECe-Booster
561
Holding register
(Protocol)
Name
Data type
Scale & unit
Elements
Access*
Added
40003
(2)
Switch box type
ENUM
0. SC
1. SC...FC
2. SCe
3. CC
4. CC...FC
5. CCe
6. SCe NWB
7. CCe NWB
8. EC
9. ECe
10. ECe NWB
R
31.000
40014
(13)
Bus command timer
ENUM
0. -
1. Off
2. Set
3. Active
4. Reset
5. Manual
RW
31.000
40015
(14)
Drives on/off
BOOL
RW
31.000
40025
(24)
Control mode
ENUM
0. p-c
1. dp-c
2. dp-v
3. dT-c
4. dT-v
5. n(TV)
6. n(TR)
7. n(TP)
8. n(TA)
9. n-c
10. fill
11. empty/drain
12. FTS
13. cleans/day
14. cleans/
month
R
31.000
40026
(25)
Current value
INT16
0.1 bar
0.1 m
0.1 K
0.1 °C
1 cm
1 min
0.1 h
0.1 psi
R
31.000
40041
(40)
Pump 1 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40042
(41)
Pump 2 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40043
(42)
Pump 3 mode
ENUM
0. Off
1. Hand
2. Auto
RW
31.000
40062
(61)
Switch box state
BITMAP
0: SBM
1: SSM
R
31.000
40139 - 40140
(138-139)
Error state
BITMAP32
0: Sensor error
1: P max
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
R
31.000
Содержание Control EC-Booster
Страница 2: ......
Страница 46: ...de Anhang 46 WILO SE 2019 07 Legende R nur Lesezugriff RW Lese und Schreibzugriff ...
Страница 434: ...hr Dodatak 434 WILO SE 2019 07 Legenda R samo pristup za čitanje RW pristup za čitanje i pisanje ...
Страница 606: ...nl Bijlage 606 WILO SE 2019 07 Legenda R alleen leestoegang RW lees en schrijftoegang ...
Страница 692: ...pl Załącznik 692 WILO SE 2019 07 Legenda R tylko dostęp odczytu RW dostęp odczytu i zapisu ...
Страница 736: ...pt Anexo 736 WILO SE 2019 07 Legenda R só para acesso de leitura RW acesso de leitura e escrita ...
Страница 1208: ......
Страница 1209: ......
Страница 1210: ......