Installation
en
Installation and operating instructions Wilo-Control EC/ECe-Booster
63
Fig. 19:
Connection overview symbol
A fault message is output for all pumps (SSM) via a separate output:
▪ Contact type: potential-free changeover contact
▪ Contact load:
– Minimum: 12 V, 10 mA
– Maximum: 250 V, 1 A
Insert the connection cable laid by the customer through the threaded cable glands and
secure. Connect the wires to the terminal strip according to the connection diagram.
Use the terminal number shown in the connection overview in the cover.
6.5.15
Individual run signal (EBM) con-
nection
DANGER
Risk of fatal injury due to an external electrical current source!
The power supply comes from an external source. This voltage is also present at the
terminals when the main switch is switched off! There is a risk of fatal injury! The
power supply must be disconnected from its source before commencing any work!
Electrical work must be carried out by a qualified electrician in accordance with the
locally applicable regulations.
x
Fig. 20:
Connection overview symbol
A run signal is output for each pump (EBM) via a separate output:
▪ Contact type: potential-free NO contact
▪ Contact load:
– Minimum: 12 V, 10 mA
– Maximum: 250 V, 1 A
Insert the connection cable laid by the customer through the threaded cable glands and
secure. Connect the wires to the terminal strip according to the connection diagram.
Use the terminal number shown in the connection overview in the cover.
The num-
ber shown in location “x” on the symbol indicates which pump it refers to:
▪ 1 = pump 1
▪ 2 = pump 2
▪ 3 = pump 3
6.5.16
Individual fault signal (ESM) con-
nection
DANGER
Risk of fatal injury due to an external electrical current source!
The power supply comes from an external source. This voltage is also present at the
terminals when the main switch is switched off! There is a risk of fatal injury! The
power supply must be disconnected from its source before commencing any work!
Electrical work must be carried out by a qualified electrician in accordance with the
locally applicable regulations.
x
Fig. 21:
Connection overview symbol
A fault message is output for each pump (ESM) via a separate output:
▪ Contact type: potential-free NC contact
▪ Contact load:
– Minimum: 12 V, 10 mA
– Maximum: 250 V, 1 A
Insert the connection cable laid by the customer through the threaded cable glands and
secure. Connect the wires to the terminal strip according to the connection diagram.
Use the terminal number shown in the connection overview in the cover.
The num-
ber shown in location “x” on the symbol indicates which pump it refers to:
▪ 1 = pump 1
▪ 2 = pump 2
▪ 3 = pump 3
Содержание Control EC-Booster
Страница 2: ......
Страница 46: ...de Anhang 46 WILO SE 2019 07 Legende R nur Lesezugriff RW Lese und Schreibzugriff ...
Страница 434: ...hr Dodatak 434 WILO SE 2019 07 Legenda R samo pristup za čitanje RW pristup za čitanje i pisanje ...
Страница 606: ...nl Bijlage 606 WILO SE 2019 07 Legenda R alleen leestoegang RW lees en schrijftoegang ...
Страница 692: ...pl Załącznik 692 WILO SE 2019 07 Legenda R tylko dostęp odczytu RW dostęp odczytu i zapisu ...
Страница 736: ...pt Anexo 736 WILO SE 2019 07 Legenda R só para acesso de leitura RW acesso de leitura e escrita ...
Страница 1208: ......
Страница 1209: ......
Страница 1210: ......