en
Commissioning
70
WILO SE 2019-07
Fig. 31:
Menu 5.11
Menu no.
5.11
Description
Pressure sensor measurement range
Value range
1 … 25 bar
Factory setting
16 bar
Fig. 32:
Menu 5.14
Menu no.
5.14 (Control ECe-Booster only)
Description
PID controller: Proportional factor
Value range
0.1 … 100
Factory setting
2.5
Explanation
Fig. 33:
Menu 5.15
Menu no.
5.15 (Control ECe-Booster only)
Description
PID controller: Integral factor
Value range
0 … 300
Factory setting
0.5
Explanation
Fig. 34:
Menu 5.16
Menu no.
5.16 (Control ECe-Booster only)
Description
PID controller: Differential factor
Value range
0 … 300
Factory setting
0
Explanation
Fig. 35:
Menu 5.40
Menu no.
5.40
Description
Switch “pump kick” function On/Off
Value range
off, on
Factory setting
on
Fig. 36:
Menu 5.41
Menu no.
5.41
Description
Allows “pump kick” when status is Extern OFF
Value range
off, on
Factory setting
on
Fig. 37:
Menu 5.42
Menu no.
5.42
Description
“Pump kick” interval
Value range
1 … 336 h
Factory setting
24 h
Содержание Control EC-Booster
Страница 2: ......
Страница 46: ...de Anhang 46 WILO SE 2019 07 Legende R nur Lesezugriff RW Lese und Schreibzugriff ...
Страница 434: ...hr Dodatak 434 WILO SE 2019 07 Legenda R samo pristup za čitanje RW pristup za čitanje i pisanje ...
Страница 606: ...nl Bijlage 606 WILO SE 2019 07 Legenda R alleen leestoegang RW lees en schrijftoegang ...
Страница 692: ...pl Załącznik 692 WILO SE 2019 07 Legenda R tylko dostęp odczytu RW dostęp odczytu i zapisu ...
Страница 736: ...pt Anexo 736 WILO SE 2019 07 Legenda R só para acesso de leitura RW acesso de leitura e escrita ...
Страница 1208: ......
Страница 1209: ......
Страница 1210: ......