Commissioning
en
Installation and operating instructions Wilo-Control EC/ECe-Booster
73
Menu 1: Values for switching on and off
Fig. 52:
Menu 1.01
Menu no.
1.01
Description
Pressure setpoint
Value range
0.1 … 25.0* bar
Factory setting
4 bar
Explanation
* The maximum value is dependent on the set measure-
ment range of the pressure sensor (Menu 5.11).
Fig. 53:
Menu 1.04
Menu no.
1.04
Description
Activation threshold of the pump in % of the pressure set-
point
Value range
75 … 99 %
Factory setting
95 %
Fig. 54:
Menu 1.07
Menu no.
1.07
Description
Base-load pump deactivation threshold in % of pressure
setpoint
Value range
101 … 125 %
Factory setting
115 %
Fig. 55:
Menu 1.08
Menu no.
1.08 (Control EC-Booster only)
Description
Peak-load pump deactivation threshold in % of pressure
setpoint
Value range
101 … 125 %
Factory setting
110 %
Fig. 56:
Menu 1.09
Menu no.
1.09
Description
Base-load pump switch-off delay
Value range
0 … 180 s
Factory setting
10 s
Fig. 57:
Menu 1.10
Menu no.
1.10
Description
Peak-load pump activation delay
Value range
0 … 30 s
Factory setting
3 s
Fig. 58:
Menu 1.11
Menu no.
1.11
Description
Peak-load pump switch-off delay
Value range
0 … 30 s
Factory setting
3 s
Содержание Control EC-Booster
Страница 2: ......
Страница 46: ...de Anhang 46 WILO SE 2019 07 Legende R nur Lesezugriff RW Lese und Schreibzugriff ...
Страница 434: ...hr Dodatak 434 WILO SE 2019 07 Legenda R samo pristup za čitanje RW pristup za čitanje i pisanje ...
Страница 606: ...nl Bijlage 606 WILO SE 2019 07 Legenda R alleen leestoegang RW lees en schrijftoegang ...
Страница 692: ...pl Załącznik 692 WILO SE 2019 07 Legenda R tylko dostęp odczytu RW dostęp odczytu i zapisu ...
Страница 736: ...pt Anexo 736 WILO SE 2019 07 Legenda R só para acesso de leitura RW acesso de leitura e escrita ...
Страница 1208: ......
Страница 1209: ......
Страница 1210: ......