31
WIKA operating instructions process transmitter, model UPT-2x
14111166.02 04/2015 EN/DE
EN
8. Configuration via display and operating unit
24.
Go back one menu level using [ESC].
Select “Low 0%” and confirm with [↵].
25. Set the initial value of the volume measurement with respect
to 0 % of the filling height (e.g. 0 % filling height corresponds
to 3 litres).
»
The cursor moves to the next digit.
»
Repeat for each digit.
» Initial value is set.
26.
Select “High 100%” and confirm with [↵].
27. Set the end value of the volume measurement with respect
to 100 % of the filling height (e.g. 100 % filling height corre
-
sponds to 1,000 litres).
»
The cursor moves to the next digit.
»
Repeat for each digit.
» Initial value is set.
28.
Go back one menu level using [ESC].
Select “Mode” and confirm with [↵].
29.
Go back one menu levels using [ESC].
Select “Volume” and confirm with [↵].
»
Mode is set to volume.
30. Perform a mounting correction.
→ See chapter 8.5 “Mounting correction (offset)”.
» Volume measurement is configured.