49
WIKA operating instructions process transmitter, model UPT-2x
14111166.02 04/2015 EN/DE
EN
10. Detailed settings
10.7 Setting the HART
®
communication
10.7.1 Setting the short address (multidrop mode)
Setting range: 0 ... 63
1.
Open the operating menu with [↵].
Select “Detail setup” and confirm with [↵].
2.
Select “HART” and confirm with [↵].
3.
Select “Short addr.” and confirm with [↵].
4.
Change digit using [▲] [▼] and confirm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
»
Short address is set.
10.7.2 Activate/deactivate constant current
The constant current affects the output of current values, e.g. in the additional
display
1.
Open the operating menu with [↵].
Select “Detail setup” and confirm with [↵].
2.
Select “HART” and confirm with [↵].
3.
Select “Cons. current” and confirm with [↵].
3. Activate/deactivate constant current.
Select “on” or “off” and confirm with [↵].
»
Constant current is activated/deactivated.