14111166.02 04/2015 EN/DE
EN
8. Configuration via display and operating unit
8.
Configuration via display and operating unit
8.1
Configuring the measuring task
8.1.1
Configuring pressure measurement
1.
Open the operating menu with [↵].
Select “Basic setting” and confirm with [↵].
2.
Select “Application” and confirm with [↵].
3.
Select “Pressure” and confirm with [↵].
4.
Select “Unit” and confirm with [↵].
5.
Select pressure unit and confirm with [↵].
» Pressure unit is set.
6.
Go back one menu level using [ESC].
Select “Mode” and confirm with [↵].
7.
Select “Pressure” and confirm with [↵].
»
Mode is set.
8. Scale the measuring range.
→ See chapter 8.3 “Scaling the measuring range”.
9. Perform a mounting correction.
→ See chapter 8.5 “Mounting correction (offset)”.
» Pressure measurement is configured.