PROFIBUS DP gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
118
Module num-
ber
Diagnosis bit
(X_Unit_Diag_Bit)
Error cause
Error message
1
Internal error: Internal tests failed or monitoring
test failed or poor process data or self-test failed
2
External error: External tests failed
3
Error history element exists: Access with configura-
tion tool
4
Configuration is incompatible or invalid
5
Output power supply not in permitted range
6 to 7
Reserved
8
Dual-channel evaluation of input 1 - 2: Error detec-
ted
9
Dual-channel evaluation of input 3 - 4: Error detec-
ted
10
Dual-channel evaluation of input 5 - 6: Error detec-
ted
11
Dual-channel evaluation of input 7 - 8: Error detec-
ted
2
12
I/O module
Reserved
13
Reserved
14
Module state of input data
15
Module state of output data
16
Error of the external test signal at input 1. Check to
short-circuit to high or cabling error
17
Error of the external test signal at input 2. Check to
short-circuit to high or cabling error
18
Error of the external test signal at input 3. Check to
short-circuit to high or cabling error
19
Error of the external test signal at input 4. Check to
short-circuit to high or cabling error
20
Error of the external test signal at input 5. Check to
short-circuit to high or cabling error
21
Error of the external test signal at input 6. Check to
short-circuit to high or cabling error
22
Error of the external test signal at input 7. Check to
short-circuit to high or cabling error
2
23
I/O module
Error of the external test signal at input 8. Check to
short-circuit to high or cabling error
24
Error: Short-circuit after high at output 1
25
Error: Short-circuit after low at output 1
26
Error: Short-circuit after high at output 2
27
Error: Short-circuit after low at output 2
28
Error: Short-circuit after high at output 3
29
Error: Short-circuit after low at output 3
30
Error: Short-circuit after high at output 4
31
Error: Short-circuit after low at output 4
3
0
PROFIBUS ga-
teway
Reserved
1
Internal error: Internal tests failed