PROFINET IO-Gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
68
Step 3: Configure the gateway properties
Double-click the hardware symbol of the SP-COP2-ENI module.
Configure the IP address, the device name, and the update interval of the cyclical I/O data
exchange. Select the
Properties
tab for this.
NOTICE
The PLC can only communicate with the SP-COP2-ENI module if the PLC software and the gateway
use the same gateway name.
In accordance with IEC 61158-6-10 no capital letters are permitted for the symbolic name (Name-
OfStation).