CANopen gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
125
How to set the CANopen address and the baud rate with the aid of the software
Set the two hardware address switches on the front of the device to "00".
Launch samosPLAN
6.
Read in the hardware configuration, including the CANopen gateway.
Instructions: Software manual, chapter "Connecting to the safety controller"
Change to the
Modules
docking window and click the SP-CAN module in the work area.
Open the
Properties
docking window.
⇨
You see the module configuration dialog.
Under
Communication
, enter the desired values for the parameters
Controller address
and
baud rate
.
Combine samosPLAN
6 with the samosPRO system and transmit the configuration.
More detailed information on the link to the controls: Software manual, chapter "Connecting to
the safety controller"
NOTICE
• You can set an address within the 1 ... 99 range with the aid of the hardware address switches.
• You can set an address within the 1 ... 127 range with the aid of the samosPLAN
6.
• The CAN-open master cannot overwrite the address.
• When the CANopen address and the baud rate are set with the aid of samosPLAN
6 , the set-
tings become valid immediately after transferring the configuration (i.e. without first switching
the samosPRO system off and on again). Exception: When the system is in the Bus-Off state, a
power cycle is required.
Pin assignment
The connection to the CANopen field bus takes place with the aid of a 5-pin open-style plug.