PROFIBUS DP gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
109
LED
Meaning
Red
Critical error on another module
PWR
Off
No power supply
Green
Power supply switched on, no error
Red
Critical error
Table 72: Address switch of the SP-PROFIBUS-DP module
Switches
Function
× 10
Address switch 1
Rotary switch with 10 positions for setting the module address
(in tens)
× 1
Address switch 2
Rotary switch with 10 positions for setting the module address
(in units)
How to set the PROFIBUS-DP address with the aid of the hardware address switches:
Use the hardware address switches at the front of the system to set the PROFIBUS-DP address.
Switch the samosPRO system off and on again.
How to set the PROFIBUS-DP address in the software:
Set the two hardware address switches on the front of the device to "00".
Launch samosPLAN
6.
Read in the hardware configuration, including the PROFIBUS-DP gateway.
Instructions: Software manual, chapter "Connecting to the safety controller"
Open the
Modules
docking window and select the SP-PB-DP module.
Also open the
Properties
docking window.
⇨
You see the configuration dialog for the SP-PB-DP module.
Enter the desired value for the
Control address
parameter under
Communication
.
NOTICE
• You can set an address within the 1 ... 99 range with the aid of the hardware address switches.
• You can set an address within the 3 ... 125 range with the aid of the samosPLAN
6.
• The PROFIBUS master cannot overwrite the address.
• An amended address setting will only become effective once you have switched off the sa-
mosPRO system and switched it on again.
• In the online mode, you can read out the address set at the PROFIBUS-DP gateway by clicking
on the
Read
button above the
PROFIBUS address
field.