EtherNet/IP gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
104
LED States
80764171
80774411
MS (Module Status)
The SP-COP2-ENI module possesses a two-color (red/green) LED with the designation
MS
. This is the
Module Status Indicator
.
The Module Status Indicator is
dark
, if no power supply is connected. It
flashes green
if the device
has not been configured. It
turns green
if the device is running correctly. It
flashes green/red
if the
device is performing a switch-on test.
The Module Status Indicator
flashes red
if EtherNet/IP is activated and the device has detected a se-
rious, eliminable error. A faulty project file or one which does not match the hardware is classified as
a serious, eliminable error. The display
turns red
if EtherNet/IP is activated and the device has detec-
ted a serious, non-eliminable error and there is a
Critical Fault
.
Table 67: MS-LED state (Selection)
Project file
System mode
Ext. Error
MS-LED state
Doesn’t matter
Switch on
Doesn’t matter
Green -> Red
Deleted
Init
Doesn’t matter
Flashing green
Invalid
Init
Doesn’t matter
Flashing red
Valid
Idle mode
Doesn’t matter
Flashing green
Valid
Run
No
Turns green
Valid
Run
Yes
Turns green/red or flashes red
Valid
Critical error
Doesn’t matter
Turns red
80788875
NET (Network Status)
The SP-COP2-ENI module possesses a two-color (red/green) LED with the designation
NET
. This is
the
Network Status Indicator
.
Table 68: Meaning of the NET LED (used as EtherNet/IP gateway)
NET LED
Meaning / reason
LED off
• Power supply not connected.
or
• Power supply connected but IP address not configured.
Green (1 Hz)
EtherNet/IP has been activated and an IP address has been configured but there is
no CIP connection and an “Exclusive Owner” connection has not yet shown a time-
out.
Green
An IP address has been configured, there is at least one CIP connection (of any
transport class) and an “Exclusive Owner” connection has not yet shown a time-out.
/
Red/gr
een
During power-on test
Red
EtherNet/IP has been activated, an IP address has been configured and an “Exclusi-
ve Owner” connection, for which the device is the target device, has shown a time-
out.
The Network Status Indicator is
dark
if no power supply is connected or a power supply is connected
but no IP address is configured (interface configuration attribute of the TCP/IP interface object). It
flashes green
if EtherNet/IP is activated and an IP address has been configured but no CIP connec-
tion is available and an “Exclusive Owner” connection has not yet shown a time-out. It
turns green
if
8.9.2
8.9.2.1
8.9.2.2