page A – 12
AirAura X1 / Dec 2016
A P P E N D I C E S
In the above circuits the external devices are powered by a customer-supplied 12V
DC power supply. When relays are interfaced it is recommended to use the reverse biased
diode shown across each relay coil. The diode harmlessly dissipates the voltage “kickback”
generated when the relay coil is de-energized. Unsuppressed, such kickback voltages can
harm the X1, external circuitry, or both.
In the top circuit the relay is activated if GPO#4 goes true to warn of a General System
Failure.
In the middle circuit the LED illuminates when GPO #3 goes true to warn of a System
Temperature above 50C (122F).
In the bottom circuit the relay is activated by GPO #2 to warn of a Digital Audio failure.
No connections were made to the terminals for GPO #1, the Analog audio source
failure warning.
Example Schematic of General Purpose Outputs