5/12/2017
TECH-538/D.W.O. 23160
Page 162 of 189
Index
Parameter
mnemonic
Description / EDD Help
Valid Range
Default
FCT Default
Deep
Default
Units
Write
R/W
39
TRK_VAL
This input is used as the track value when external tracking is
enabled by TRK_IN_D.
TRK
40
FF_VAL
The feed forward value and status.
FF
41
FF_SCALE
The feedforward input high and low scale values, engineering
units code, and number of digits to the right of the decimal
point.
0-100%
FF
42
FF_GAIN
The gain that the feed forward input is multiplied by before it
is added to the calculated control output.
0
43
UPDATE_EVT
This alert is generated by any change to the static data.
44
BLOCK_ALM
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status attribute.
As soon as the Unreported status is cleared by the alert
reporting task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
45
ALARM_SUM
The current alert status, unacknowledged states, unreported
states, and disabled states of the alarms associated with the
function block.
46
ACK_OPTION
Selection of whether alarms associated with the block will be
automatically acknowledged.
0: Auto Ack Disabled
1: Auto Ack Enabled
0
47
ALARM_HYS
Amount the PV must return within the alarm limits before the
alarm condition clears. Alarm Hysteresis is expressed as a
percent of the PV span.
0 to 50 Percent
0.5%
%
48
HI_HI_PRI
Priority of the high high alarm.
0 to 15
0
49
HI_HI_LIM
The setting for high high alarm in engineering units.
+INF
PV
50
HI_PRI
Priority of the high alarm.
0 to 15
0
51
HI_LIM
The setting for high alarm in engineering units.
+INF
PV
52
LO_PRI
Priority of the low alarm.
0 to 15
0
53
LO_LIM
The setting for the low alarm in engineering units.
-INF
PV
54
LO_LO_PRI
Priority of the low low alarm.
0 to 15
0
55
LO_LO_LIM
Priority of the low low alarm.
-INF
PV
56
DV_HI_PRI
Priority of the high deviation alarm.
0 to 15
0
57
DV_HI_LIM
The setting of the high deviation alarm limit in engineering
units.
+INF
PV
58
DV_LO_PRI
Priority of the low deviation alarm.
0 to 15
0
59
DV_LO_LIM
The setting of the low deviation alarm limit in engineering
units.
-INF
PV
60
HI_HI_ALM
The status for high high alarm and its associated time stamp.
PV
61
HI_ALM
The status for high alarm and its associated time stamp.
PV
62
LO_ALM
The status of the low alarm and its associated time stamp.
PV
63
LO_LO_ALM
The status of the low low alarm and its associated time stamp.
PV
64
DV_HI_ALM
The status and time stamp associated with the high deviation
alarm.
PV
65
DV_LO_ALM
The status and time stamp associated with the low deviation
alarm.
PV
66
BLOCK_ERR_DESC_1 Specific details of a BLOCK_ERR.
Read only