5/12/2017
TECH-538/D.W.O. 23160
Page 118 of 189
Diagnostic parameters that measure time are not working
1)
If parameters like STROKE_TIME_CLOSED or STROKE_TIME_OPEN are not updating, check the
mode block of the Transducer block that needs to be AUTO.
2)
Host system refreshing problems: Close and reopen the parameter window to update the values.
Valve position is not being maintained within the deadband range
The deviation deadband range (EDb) is set from the configuration menu during calibration (see sections
8.9.7.1, 8.10.4.1 and 8.12.2). The EDb must be set to other than zero (0) to enable the Alert 3 message.
Additionally, check the following items:
•
Position Sensor connector and cable, especially if remote
•
Pressure supply stability
•
Actuator and tubing leaks
•
Magnet assembly in correct position and tight
•
Set-point stability
•
Flow turbulence
•
Sources of electromagnetic noise too close to the sensor or to the positioner cables, like AC cables
for motors, inverters, etc.