Index
Std.
Par.
Parameter mnemonic
Description / EDD Help
Valid Range
FF Default
FCT Default
Deep
Default
Units
Write
R/W
101
INTERNAL_TEMP_MIN
Minimum internal device
temperature in user defined
temperature units over operation
lifetime of device.
-40 to +185
22
ITU
Read
only
102
INTERNAL_TEMP_MAX
Maximum internal device
temperature in user defined
temperature units over operation
lifetime of device.
-40 to +185
22
ITU
Read
only
103
INTERNAL_TEMP_UNITS
Internal temperature units as defined
in standard table in (TN-016).
Only accepts oC and
oF
oC
oC
oC
ITU
R/W
104
BLOCK_ERR_DESC_1
New field diagnostics for ITK6.
Read
only
105
COMM_DIAG_TPTO
Token Pass Timeout
Integer 32 bits
0
0
0
Read
only
106
FLOP_ENABLE
Fail open / close position reference.
0: Flop Enable Off
1: Flop Enable On
Flop Enable Off
Flop Enable
Off
Flop Enable
Off
107
SERVO_GAIN
Proportional gain
Float 32 bits
108
SERVO_RESET
Integral gain
0 – 256
109
SERVO_RATE
Derivative gain
0 - 256
110
VALVE_OPEN_SLEW_LIMIT
Open speed configuration
111
VALVE_CLOSE_SLEW_LIMIT
Close speed configuration
112
PSNR_RESET_COUNTERS
Reset the following alert counters:
CYCLE_CNTR, TRAVEL_ACCUM,
TEMP_MAX_MIN, TPTO, CAL_ERROR,
RUN_TIME_ERROR, RESERVED.
0x01-0x80
113
XD_ALERT_ENABLE
0x0001, "CYCLE_CNTR" , "Enable
Cycle Count Alarm
0x0002, "TRAVEL_ACCUM" , "Enable
Travel Accumulator Alarm
0x0004, "TEMP_MAX_MIN" , "Enable
Maximum Temperature Alarm
0x0008, "DEVIATION" , "Enable SP
Deviation Alarm
0x01-0x08
114
PSNR_ALERT_SUMMARY
0x0001, "DEVIATION", "SP Deviation
Alarm,
0x0002, "CYCLE_LIMIT", "Cycle Count
Alarm ,
0x0004, "TRAVEL_ACCUM", "Travel
Accum. Alarm,
0x0008, "TEMP_MAX_MIN",
"Maximum Temperature Alarm,
0x0010, "CLOGGED NOOZLE", "Flap-
Nozzle clogged Alarm,
0x0020, "LOW PRESSURE", "Low
Pressure Alarm",
0x0040, "STEADY ERROR", "Steady-
State Position Error Alarm ",
0x0080, "CAL ERROR", "Calibration
0x0001-0x0100
Read
only