5/12/2017
TECH-538/D.W.O. 23160
Page 159 of 189
Index
Parameter
mnemonic
Description / EDD Help
Valid Range
Default
FCT Default
Deep Default
Units
Write R/W
21
SP_LO_LIM
The revision level of the static data associated with the function
block. The revision value will be incremented each time a static
parameter value in the block is changed.
PV/- 10%
0
PV
Read
only
22
CHANNEL
The number of the logical hardware channel that is connected to
this I/O block. This information defines the transducer to be used
going to or from the physical world.
See Table 18
0 - Channel
0
23
FSTATE_TIME
The time in seconds from detection of failure of the output block
remote setpoint to the output action of the block output if the
condition still exists.
Positive or zero
0
Sec
24
FSTATE_VAL
The preset analog working setpoint value to use when fault
occurs. This value will be used if the I/O option Fault State to
value is selected.
PV/- 10%
0
PV
25
BKCAL_OUT
The value and status required by an upper block’s BKCAL_IN so
that the upper block may prevent reset windup and provide
bumpless transfer to closed loop control.
PV
Read
only
26
RCAS_IN
Target setpoint and status provided by a supervisory Host to an
analog control or output block.
PV
27
SHED_OPT
Defines action to be taken on remote control device timeout.
28
RCAS_OUT
Block setpoint and status after ramping - provided to a
supervisory Host for back calculation and to allow action to be
taken under limiting conditions or mode change.
PV
Read
only
29
UPDATE_EVT
This alert is generated by any change to the static data.
Read
only
30
BLOCK_ALM
The block alarm is used for all configuration, hardware,
connection failure, or system problems in the block. The cause of
the alert is entered in the subcode field. The first alert to become
active will set the Active status in the Status attribute. As soon as
the Unreported status is cleared by the alert reporting task,
another block alert may be reported without clearing the Active
status, if the subcode has changed.
Read
only
31
XDUCER_VAL
The value and status received from the Transducer block on the
selected channel.
32
BLOCK_ERR_DESC_1
Specific details of a BLOCK_ERR.
Read
only
33
SUPPORTED_MODES
Read only parameter that indicates the modes supported by the
block.
0x08: Automatic
(Auto)
0x10: Manual
(Man)
0x80: Out of
Service (O/S)
Read
only