5/12/2017
TECH-538/D.W.O. 23160
Page 15 of 189
•
Environmental:
o
Operating/Storage: -
40˚C to +85˚C (
-
40˚F to +185˚F).
Valid for general purpose application only. Contact Westlock for hazardous areas.
Pneumatic assembly depends on media dew point.
o
Relative Humidity: 0 to 95% non-condensed.
o
Vibration: 2 g, 10Hz to 1000 Hz.
o
Shock: 18 g, 3 axis, 100 bumps each axis.
o
References: IEC61514-2, IEC 60068-2-29/27, IEC 61298-3, IEC 60068-2-1/2.
•
Ingress Protection rating (base models):
o
6400 Aluminum Housing:
IP66
o
6400 SST Housing :
IP66
o
Contact Westlock on other models
•
Electro-Magnetic Compatibility (EMC):
Table 3:
ICoT 6000 Series – EMC Immunity Test
Immunity Test
Standard
Level
Class
Electrostatic Discharge - ESD
IEC 61000-4-2
Direct ±4kV, air ±8kV
A
Electric Fast Transient Burst – EFTB
IEC 61000-4-4
±2kV
A
Lightning Surge - SURGE
IEC 61000-4-5
±1kV
A
Power Frequency Magnetic Field –
PFMF
IEC 61000-4-8
30A/m 50Hz and 60Hz
A
Radiated Immunity – RI
IEC 61000-4-3
10 V/m 80MHz-1GHz
3 V/m 1GHz-2.7GHz
A
Conducted Immunity - CI
IEC 61000-4-6
10Vrms 150kHz-80MHz
A
Table 4:
ICoT 6000 Series – EMC Emissions Test
Emissions Test
Standard
Level
Class
Radiated Emissions – RE
CISPR 11
Class A QP 3m
A
Conducted Emissions - CE
CISPR 22
Class A
A
8
Class A: device does not exhibit noticeable interference. Class B: device may exhibit temporary
interference or with loss of function, but self-recovers. Reference standards: IEC 61514-2, IEC61326,
IEC61000-6-4, IEC61000-6-2.