20
an approved container, seal it and dispose of it in accordance with local regulations. Do
not pour on the ground or put in drains.
If severe sludge or trash formed in the interstice, it is recommended that the inner tank be
removed and the outer tank be completely washed out. Do not take chances with
contaminating the workplace or the environment.
d.
Monthly:
Lubricate the door hinge and lock.
Clean out pump and line filters including strainer.
Visually check tank, hoses, valves, pump and other components for cracks, corrosion
and leakage.
Correct all deficiencies before starting. Stop leaks. Make repairs using only genuine
replacement parts or their equivalent.
4.7 CLEANING
Each owner and user of the
FUEL
CUBE
TM
should review this manual as part of the regular
training and review procedure. Follow all instructions.
1.
Remove the corner brackets and bolts from each side.
2.
Screw in lifting eyes into sockets on the top of the tank.
3.
With the inner tank emptied of fuel, attach lifting system and lift tank straight up.
4.
Clean the inside of the outer tank (bund). Remove all debris and liquids.
5.
Pressure wash out the tank, drain tank, and then dry. An internal inspection can now be
made.
It is recommended the leak test is carried out after the internal inspection. Replace
pressure/vacuum relief valve with a plug for the leak test. Reassemble the tank in reverse order.
Install a new pressure/vacuum relief valve that is available from Western International Inc.
Leak proof test at 20 kPa (3 psi) for 10 minutes.
Keep records of testing with the unit at all times.