![Weishaupt W-FM 25 Скачать руководство пользователя страница 56](http://html.mh-extra.com/html/weishaupt/w-fm-25/w-fm-25_manual_953369056.webp)
4. Deactivate E-Parameters
Burner must be in Standby (
OFF
).
▶
Press [Enter] and [+] keys simultaneously for approx. 2 seconds.
✓
The parameter level is activated.
▶
Press [+].
▶
Press [Enter] key until parameter
E
is displayed.
▶
Set parameter
E
to
OFF
.
✓
E
-Parameters are not shown in the setting level.
▶
Press [Enter] key twice.
✓
Combustion manager returns to the operating level.
Installation and operating instruction
Replacing combustion manager W-FM 20 … 24 with W-FM 25
6 Commissioning
83294002 • 2/2014-11 • La
56-70
Содержание W-FM 25
Страница 71: ...83294002 2 2014 11 La ...