![Weishaupt W-FM 25 Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/weishaupt/w-fm-25/w-fm-25_manual_953369035.webp)
▶
Press [+].
✓
Burner starts according to the sequence of operation and stops at operating
point P
0
(ignition load).
▶
Check combustion and if necessary adjust via air damper or gas butterfly setting.
▶
Press [+].
✓
Burner drives to P
1
.
▶
Check combustion and if necessary adjust via air damper or gas butterfly setting.
▶
Press [+].
✓
Burner drives to P
2
.
▶
Determine the air damper and gas butterfly valve setting for operating point P
2
.
▶
Preset P
2
with these values.
▶
Check combustion and if necessary adjust via air damper or gas butterfly setting.
▶
Repeat steps for each operating point until P
9
has been reached.
4. Adjust full load
▶
Press [G] and [L/A] simultaneously.
✓
Burner drives to full load.
✓
The upper operating limit (
bo
) is displayed.
If necessary, full load can be adjusted using [–] or [+] keys.
Installation and operating instruction
Replacing combustion manager W-FM 20 … 24 with W-FM 25
6 Commissioning
83294002 • 2/2014-11 • La
35-70
Содержание W-FM 25