4. Adjust full load
▶
Press [+] key until P
9
is reached whilst checking combustion at each point.
▶
Press [G] and [L/A] simultaneously.
✓
Burner drives to full load.
✓
The upper operating limit (
bo
) is displayed.
If necessary, full load can be adjusted using [–] or [+] keys.
5. Adjust partial load
▶
Press [G] and [L/A] simultaneously.
✓
Burner drives to partial load.
✓
The lower operating limit is displayed (
bu
).
If necessary, partial load can be adjusted using [–] or [+] keys.
▶
Press [G] and [L/A] simultaneously.
✓
Combustion manager changes to operating level (
10
).
✓
Combustion manager is programmed.
6. Check start behaviour
▶
Switch off and restart burner.
▶
Check start behaviour and if necessary correct ignition load (P
0
).
If the ignition load set has been changed:
▶
Re-check start behaviour.
7. Deactivate E-Parameters
Burner must be in Standby (
OFF
).
▶
Press [Enter] and [+] keys simultaneously for approx. 2 seconds.
✓
The parameter level is activated.
▶
Press [+].
▶
Press [Enter] key until parameter
E
is displayed.
▶
Set parameter
E
to
OFF
.
✓
E
-Parameters are not shown in the setting level.
▶
Press [Enter] key twice.
✓
Combustion manager returns to the operating level.
Installation and operating instruction
Replacing combustion manager W-FM 20 … 24 with W-FM 25
6 Commissioning
83294002 • 2/2014-11 • La
41-70