Gas burner with speed control
The service level gives information about:
▪
Actuator position of individual operating points
▪
The most recent fault
▪
Flame signal during operation.
▶
Press [ENTER] key for approx. 2 seconds.
✓
The service level is activated.
▶
Press [Enter] to reach the next information.
No.
Information
0
Fan speed and air damper setting in operating point P
0
1
Fan speed and air damper setting in operating point P
1
9
Fan speed and air damper setting in operating point P
9
10
…
18
most recent fault … ninth last occurred fault
Display additional information:
1. Detailed fault code / operating phase
▶
Press [+] key.
2. Detailed fault code
▶
Press keys [+] and [-] simultaneously.
3. Detailed fault code
▶
Press key [L/A].
Repetition counter
▶
Press key [G].
19
Flame signal:
00
= no flame ...
58
= high intensity
After information
19
or a waiting time of approx. 20 seconds the combustion manager
changes over to the operating level.
Installation and operating instruction
Replacing combustion manager W-FM 20 … 24 with W-FM 25
4 Operation
83294002 • 2/2014-11 • La
21-70
Содержание W-FM 25