![Weishaupt W-FM 25 Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/weishaupt/w-fm-25/w-fm-25_manual_953369043.webp)
▶
Press [+].
✓
E2
is displayed.
▶
Set value
2
(flame sensor QRB) using [ENTER] and [+] key.
▶
Press [+].
✓
E3
is displayed.
▶
Adopt value
1
(fan control), if necessary set using [ENTER] and [-] or [+] key.
▶
Press [+].
✓
E4
is displayed.
▶
Adopt value
0
(no ignition delay), if necessary set using [ENTER] and [-].
▶
Press [+].
✓
Combustion manager changes into the setting level for step points.
▶
Determine the air damper setting for operating points P
9
, P
1
P
0
and P
2
from the
sticker for burner setting.
The operating points are preset using these values:
▶
Press [+].
✓
Factory setting operating point P
9
(Full load) is displayed.
▶
Press and hold [L/A] and set air damper setting using the [–] or [+] key.
Installation and operating instruction
Replacing combustion manager W-FM 20 … 24 with W-FM 25
6 Commissioning
83294002 • 2/2014-11 • La
43-70
Содержание W-FM 25
Страница 71: ...83294002 2 2014 11 La ...