Press [+].
✓
E1
is displayed.
The value of parameter
E1
can not be altered.
▪
0
= intermittent operation (Standard)
▪
1
= continuous operation (only if W-FM 21was used previously)
▶
Press [+].
✓
E2
is displayed.
▶
Adopt value
0
(ionisation electrode), if necessary adjust using [ENTER] and [-] key.
▶
Press [+].
✓
E3
is displayed.
▶
Adopt value
1
(fan control), if necessary set using [ENTER] and [-] or [+] key.
▶
Press [+].
✓
Combustion manager changes into the setting level for step points.
▶
Determine the air damper setting and fan speed for operating points P
0
, P
1
and
P
9
from the sticker for burner setting.
The operating points are preset using these values:
▶
Press [+].
✓
Factory setting operating point P
9
(Full load) is displayed.
▶
Press and hold [L/A] and set air damper setting using the [–] or [+] key.
▶
Press and hold [G] and set fan speed using [–] or [+] key.
Installation and operating instruction
Replacing combustion manager W-FM 20 … 24 with W-FM 25
6 Commissioning
83294002 • 2/2014-11 • La
38-70