Part number 550-143-010/1021
39
GV90+
series
2
gas-fired water boiler – boiler manual
Allowable vent/air pipe materials &
lengths
Use only the vent materials and kits
listed in
. Provide
pipe adapters if specified.
Locate the termination such that the total air pip-
ing and vent piping from the boiler to the termina-
tion will not exceed the maximum length given in
Determine termination location
1. The air and vent terminations must be in-
stalled as shown in
and
.
2. The terminations must comply with clearances
and limitations shown in
3. Locate the terminations so they are not likely
to be damaged by foreign objects, such as
stones or balls, or subject to buildup of leaves
or sediment.
Do not exceed the maximum lengths
of the outside vent piping shown
in
. Excessive
length exposed to the outside could
cause freezing of condensate in the
vent pipe, resulting in potential
boiler shutdown. In extremely cold
climates, install an insulated chase
around the vent piping, particu-
larly when using longer lengths. The
chase must allow for inspection of
the vent pipe, and insulation must
be protected from water.
Multiple vent/air terminations
1. When terminating multiple GV90+ boilers,
terminate each vent/air connection as de-
scribed in this manual.
All vent pipes and air inlets must
terminate at the same height to avoid
possibility of severe personal injury,
death or substantial property dam-
age.
2. Place wall penetrations to obtain minimum
clearances shown in
for
U. S. installations. For Canadian installations,
provide clearances required by CSA B149.1
Natural Gas and Propane Installation Code
or B149.2 Installation Code.
3. The air inlet of a GV90+ boiler is part of a
direct vent connection. It is not classified as a
forced air intake with regard to spacing from
adjacent boiler vents.
4. Combustion air (NOT vent piping) can be
manifolded as shown in
.
Figure 47
INSTALLATION SEQUENCE
— Separate pipes sidewall
Step 1
Read and follow all instructions in this manual.
DO NOT proceed
with vent/air installation until you have read
through
.
Step 2
Install the boiler in a location that allows proper routing of all vent and
air piping to the selected sidewall location.
Step 3
Make sure the selected sidewall termination location complies with
. (Multiple boiler sidewall plates must also comply
.)
Step 4
Use only the vent materials listed in
. Provide pipe
adapters where required. Vent piping and air piping lengths must not
exceed the values shown in
.
Step 5
Prepare the sidewall penetrations and secure the sidewall plates as
instructed in this section. See
“Prepare wall penetrations” on page 40
Step 6
The air piping must terminate in a
down-turned elbow
as shown
above. The vent piping must terminate in an
elbow pointed outward
or away from the air inlet
as shown above. See illustration above.
Step 7
Install vent and air piping between the boiler and the sidewall openings.
Slope horizontal piping downward toward the boiler at least 1/4 inch per
foot. See
for general guidelines.
Step 8
Install pipe supports every 5 feet on both the horizontal and vertical
runs. Install a hanger support within 6 inches of any upturn in the piping.
Step 9
Attach the vent termination exterior piping: Use either of the configura-
tions shown above, as needed to ensure clearance above grade or snow
line. Keep vents/air intake area clear of accumulating snow.
Step 10
The vent and air pipes may run up as high as 4 feet with no enclosure. The
vent and air pipes must be secured with braces, and all clearances and
lengths must be maintained. Space braces no further than 24 inches apart.
Step 11
External venting greater than 4 feet requires an insulated enclosure
around the vent and air pipes. The vent and air terminations must exit
through the enclosure as shown in the illustration above, maintaining
all required clearances.
DIRECT VENT —
Sidewall with separate pipes