Remove one wire and check Thermal switch on recuperator
and Block limit switch for continuity. If either switch is open,
Investigate the cause, correct and replace defective switch.
•
Remove BLOWER plug (
, Item 3) from
plug receptacle of IBC.
•
Place voltmeter leads across the 120 VAC N and
120 VAC H pins of the BLOWER receptacle.
Does the voltmeter indicate 120 VAC?
No
Yes
CHART 3
PRESS SWITCH & POWER lights flashing
Electrical shock hazard
— Wherever you see TURN OFF POWER, follow the instructions. Failure to fol
-
low instructions could result in severe personal injury, death or substantial property damage.
•
Reset boiler control by turning off power at service switch or
turning down thermostat for at least 45 seconds.
•
Thermostat should call for heat and appropriate zone valves
open.
Does blower motor operate?
No
Yes
•
Replace IBC.
•
Retest.
•
.
•
Replace if necessary.
•
Retest.
•
Clear passages and recycle boiler.
•
Recheck boiler operation.
•
Properly position blower
wheel on blower motor
shaft and tighten set screw.
(Or replace blower housing
assembly.)
•
Retest.
•
TURN OFF POWER
at
service switch.
•
Properly position blower
wheel on blower motor
shaft and tighten set screw.
(Or replace blower housing
assembly.)
•
Retest.
•
Boiler should be in normal operating se
-
quence (
•
Observe operation until thermostat is satis
-
fied and blower has completed its post-
purge cycle.
•
Replace blower motor.
(Also check blower
housing assembly.
Replace if necessary.)
•
Retest.
•
Drain condensate.
•
Retest.
•
TURN OFF POWER
at service switch.
Does blower wheel turn freely by hand?
No
Yes
•
Remove one of the red wires connected to the pressure
switch.
•
Check continuity across the switch terminals.
Does the ohmmeter indicate the switch is closed?
No
Yes
Is blower wheel turning at speed of blower motor?
No
Yes
Is blower wheel turning at speed of blower motor?
No
Yes
•
Check condensate trap.
Is there condensate present?
No
Yes
Are vent or combustion air
passages blocked?
No
Yes
•
Wait 5 minutes.
Is purge light flashing?
No
Yes
Troubleshooting