background image

9 of 11

WX-501-0544 • 01.22

Setting

Description

Command

Allows you to set the command sent from the device during the autobaud process. This option is 

currently not available.

Response

Shows the response the device is expecting from the above command. This option is currently not 

available.

SmartSensor ID

Shows the ID number of the sensor with which the Click device is currently communicating. This 

option is currently not available.

Server/Client

Allows you to set whether the device is a server or client in a point to multipoint setup (this option is 

not related to device autobauding). This option is currently not available.

The other tab is the 

513

 tab. If you click on it, you will see tabs labeled 

General

Approaches

Lanes

, and 

Output

The 

513 > General

 tab allows you to configure general settings for the Click 513 (see the figure and table below).

Setting

Description

Sensor ID

The sensor ID number for the SmartSensor HD connected to the Click 513.

Sensor Interval

This is the number of seconds that the sensor stores Interval data. This field is read only.

Alert On Time (Multiple 

of Sensor Interval)

Allows you to enter the number of intervals the Click 513 will use to determine alert status.

Alert Off Time (Multiple 

of Sensor Interval)

Sets the minimum number of qualified intervals needed (out of the monitored intervals) to turn 

off an alert.

Example.

 If Alert On Time = 1 and Alert Off Time = 2, an alert will turn on when one interval meets 

the requirements and will turn off when those requirements are not met for two intervals.

Logic

Allows you to select the logic used to qualify an interval (AND requires all enabled conditions 

to be true; OR requires only one enabled condition to be true).

Poll Interval (ms)

Allows you to enter the number of milliseconds you want to the Click 513 to wait before it polls 

for Interval Data.  The longer the interval the bigger this number can be. This field is currently 

Ready only.

The 

513 > Approach

 (Approach 1, 2, 3, and 4) tabs allow you to set the threshold values for the interval data (see 

the figure and table below for examples.)

Note. 

Values in Click Supervisor will be displayed according to the units (English or metric) selected in SSMHD.

Содержание Click 513

Страница 1: ...mp If the interval data polled from the SmartSensor HD exceeds the threshold value s the Click 513 will send an alert so that adjustments can be made to help clear the congested roadway such as keepin...

Страница 2: ...program such as Windows HyperTerminal Warning With older versions of the Click 500 series module it is necessary to remove pin 4 from the serial cable to prevent the device from going into Program mo...

Страница 3: ...t side of the module for programming or reprogramming the unit For all standard Click 513 applications the rest of the DIP switches are unused Warning The sixth switch of DIP switch 1 controls the mod...

Страница 4: ...ctive power and RS 485 communication When using multiple Click 513 modules for one DMS the devices can be wired together so that only one Click 513 will be sending an output to the DMS at a time See k...

Страница 5: ...once the desired option is displayed 6 Press the push button again to select the option The mode will now start running Run Mode blue solid Run mode is the first mode presented in the mode selection p...

Страница 6: ...2 114 device via the RS 485 top front port When using a Click 104 you will need to use a gray T bus to isolate communications sent from the RS 485 top front port so they do not collide with communicat...

Страница 7: ...ure the Click 513 The driver is divided into two tabs System and 513 The System tab is divided into three subtabs General Comm and Autobaud The General subtab contains information about the device see...

Страница 8: ...nfigure how the Click device communicates see the figure and table below Setting Description Baud Rate Allows you to change the baud rate at which the device connects to the sensor Flow Control Is use...

Страница 9: ...of seconds that the sensor stores Interval data This field is read only Alert On Time Multiple of Sensor Interval Allows you to enter the number of intervals the Click 513 will use to determine alert...

Страница 10: ...qualify until ALL enabled criteria are met The 513 Output tab contains information about which time zone is configured for the Click 513 and when alerts will be scheduled to trigger see the figure and...

Страница 11: ...01 0544 01 22 folder created when you installed Click Supervisor under Wavetronix ClickHome Drivers 513 User You can also select Save to Device to save your settings to your Click 513 Note If you do n...

Отзывы: