Ufly Controller and BCM for Modulex EXT
CHAPTER 6: BOILER COMMUNICATIONS MODULE (BCM)
OMM-0159_A_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
47
of
83
2. Scroll to Parameter 376. This parameter defines the functionality of terminals Y2 TA/9. Set
Parameter 376 = 3 to automatically activate the BCM as a backup controller.
NOTE:
Terminals Y2 TA/9 can be used for automatic activation of BCM as a backup controller
described above
OR
for enable/disable functionality not both. See Section 4.5 for setting of
Parameter 376 for enable/disable functionality.