Ufly Controller and BCM for Modulex EXT
CHAPTER 6: BOILER COMMUNICATIONS MODULE (BCM)
OMM-0159_A_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
53
of
83
6.7 Modbus Network Wiring Diagram
A “Sample” Modbus Network wiring diagram for an AERCO ACS Master controlling BCM Slaves
is shown in Figure 6-14. Activate the terminating resistor in the last BCM on the daisy-chain loop.
DO NOT install the 1K bias resistor. Instead, activate the two bias DIP switches in the ACS.
Refer to GF-124 for the location of these switches.
C A U T I O N !
It is imperative that polarity be maintained between all Modbus Network connections. The
Network will not operate if the proper polarity is not maintained. Also, twisted-pair wiring
shields should only be terminated at the controlling Master for the Modbus Network.
Figure 6-14: AERCO BMS II Master Controlling Modulex Boiler Slaves