Ufly Controller and BCM for Modulex EXT
CHAPTER 7: BCM MODBUS AND ADDRESS ASSIGNMENTS
OMM-0159_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
64
of
83
Table 7-4: BCM Standard Holding Register Address Mapping
Modbus Data
Address
Menu Item
Units and Range
Default/(Comments)
1200
Monitor Only
0
–
100%
(Read Only) Global
modulation level from
Cascade Manager
2n00
BMM #n Error Code
(n = 0
–
7)
0
–
0xFFFF
(Read Only)
2n02
BMM #n Outlet
Temperature
(n = 0
–
7)
14°F to 212°F (-10°C to
100°C) (Value x 10)
(Read Only)
2n08
BMM #n Actual
Modulation Level (n
= 0
–
7)
0
–
100%
(Read Only)
2n10
BMM #0 Capacity
(n = 0
–
7)
0
–
255 kW
(Read Only)
2n11
BMM #n
Configuration
(n = 0
–
7)
Flag (0, 1)
0: Space Heating Only
1: Space Heating and DHW
(Read Only)
2n20
BMM #n Operating
Flags (n = 0
–
7)
Flags (0-255)
Bit 0: CH Pump direction
Bit 1: DHW Pump direction
Bit 2: CHECK mode
Bit 3: Flame detected
Bit 4: Heat request
Bit 5: Warning
Bit 6: Pump status
Bit 7: Alarm
(Read Only)
SYSTEM DATA
1550
Firmware Code &
Firmware Revision
0x2100
–
0x21FF
High byte: Firmware Code
Low byte: Firmware Revision
(Read Only)
1011
Boiler Global
Capacity
0
–
FFFF kW
(Read Only)
12
Boiler Mode =
AERCO BMS II/ACS
2
(Read Only)
13
Remote Signal =
Network
3
(Read Only)
SETTINGS
19
Modbus Address
1 - 127
(Read/Write)