Ufly Controller and BCM for Modulex EXT
CHAPTER 4: UFLY SETUP AND PROGRAMMING
OMM-0159_A_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
30
of
83
4.3.2 0-to-10-Volt Remote Setpoint Mode Operation Configuration
The 0-to-10-volt Remote Setpoint Mode is configured as follows:
1. Access
Device Management
from Main Menu; select
hcm
>
Parameter Settings
2. Scroll to Parameter 799. Set Parameter 799 = 2.
•
Parameter 799 defines the functionality of terminals 6/7 of connector Y2 on the
Input/Output box.
•
When set to “2”, the terminals will accept a 0-10V Remote setpoint input.
•
When set to “1” (Default value), the terminals will accept an outdoor air sensor – see
Chapter 4.1.