Ufly Controller and BCM for Modulex EXT
CHAPTER 6: BOILER COMMUNICATIONS MODULE (BCM)
OMM-0159_A_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
55
of
83
1. Access
Device Management
from Main Menu; select
hcm
>
Parameter Settings
2. Scroll to Parameter 803 and set its value to 16. This allows Control via Modbus such as
via AERCO ACS or BAS/EMS.
3. Scroll to Parameter 816 and set the Modbus address for this BCM.
Once the desired address has been set on each BCM, the Modulex Boiler is configured for
Modbus Network control by the controlling Master EMS/BAS or AERCO ACS. For the BCM to
automatically act as the Back-Up Controller if the Modbus Master signal is lost, Parameter 376 of
the BCM must be set to 3 and a jumper must be installed on terminals TA/9 of connector Y2 (see
section 6.3.2 for details)
See Chapter 8 and GF-124 Chapter 2 for Modbus points for the BCM and ACS.
hcm
19
803: Enabled services
483: Max differential temperature
34: Burner Hysteresis
31: CH#1: Minimum setpoint
39: CH#1: Maximum setpoint
0
°R
77
°F
185
°F
9
°R
hcm
2
799: 0/10V input
376: Input#1: function
322: Pump: overrun
341: Pump: minimum control
313: Pump: maximum control
0
3.0
Volt
10.0
Volt
5
min
hcm
19
803: Enabled services
483: Max differential temperature
34: Burner Hysteresis
31: CH#1: Minimum setpoint
39: CH#1: Maximum setpoint
0
°R
90
°F
140
°F
9
°R
16