Ufly Controller and BCM for Modulex EXT
CHAPTER 6: BOILER COMMUNICATIONS MODULE (BCM)
OMM-0159_A_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
46
of
83
Figure 6-7: Boiler Control Manager Screen
To operate the BCM as a backup controller, press the MANUAL button on the BCM controller.
The BCM can also be operated as a backup controller automatically in lieu of pressing the
MANUAL button. This is particularly useful if the normal mode of operation is via Modbus so that
if the Modbus signal is lost, the BCM will automatically act as a backup controller. To accomplish
this, a jumper must be installed on terminals TA and 9 terminal block Y2 in the Input/Output box
and Parameter 376 must be set to 3.
The function of terminals Y2 TA/9 is configured as follows:
1. Access
Device Management
from Main Menu; select
hcm
>
Parameter Settings