Ufly Controller and BCM for Modulex EXT
CHAPTER 4: UFLY SETUP AND PROGRAMMING
OMM-0159_A_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
29
of
83
3. Click the
settings
icon.
• Set the
Setpoint/OAR Max Setpoint
to desired temperature
•
Setpoint High Limit
(upper limit of setpoint) and
Setpoint Low Limit
(lower limit of
setpoint) can also be set on this screen
4.3 0-To-10-Volt Remote Set Point Mode
This mode allows the boiler set point to be controlled by an external control signal. The following
sections provide the procedures necessary to wire, configure and set the required functions
necessary to operate in the 0-to-10-volt remote set point mode.
4.3.1 Wiring Connections
Connect the 0-10V remote setpoint input to the Input/Output box, connector Y2, terminals 6
(GND) and 7 (Analog input).