Explanation of Function
Seite 122 / 180
FM terminal
The FM control terminal can monitor the output frequency and output current.
FM terminal is a PWM (Pulse Width Modulation) output.
(1) FM selection
Select a signal to output from the following options.
When 03(digital frequency) is set a digital frequency counter meter is required.
Use an analog meter for all other output signals.
Function
code
Data
Description
Full scale value
00
Output frequency (example 1)
0-Max. frequency(Hz)
01
Output current (example 1)
0-200%
02
Output torque (example 1)
0-200%
03
Digital output frequency
(example 2)
0-Max. frequency(Hz)
04
Output voltage (example 1)
0-100%
05
Input electric power (example 1)
0-200%
06
Thermal load ratio (example 1)
0-100%
C027
07
LAD frequency (example 1)
0-Max. frequency(Hz)
(2) FM adjustment
This function is used to calibrate a meter connected to the FM terminal.
Function code
Set range
Description
b081
0. -255.
Change one by one.
(calibration methods)
(1) Connect meter to FM-CM1.
(2) Adjust b081 so that the meter is reading the same as the output frequency on your scale.
(Example) When output frequency is 60Hz, change value of b081 so that meter is 60Hz.
C027: FM selection
b081: FM adjustment
Relation code
Period T: constant
(6.4m)
t
T
t
T
Period T: change
Duty t/T : 50%fixed
(Example 1) Set value:00, 01, 02, 04, 05, 06, 07
(Example 2) Set value: 03
Содержание V3000-015LF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...