Installation and Wiring
Seite 30 / 180
H
O2
AM
FM
TH
FW
8
CM1
5 3 1 14
13 11
AL1
L O OI
AMI
P24
PLC
CM1
7 6 4 2 15
CM2
12
ALO
AL2
(3)Change of input logic type
The logic type of intelligent input terminals is sink type (Factory Default).
To change the input logic type into source type, take off the short bar between P24 and PLC on the control terminal
and connect it between PLC and CM1.
The terminal screw size; M3