Explanation of Function
Seite 78 / 180
Frequency limiter
This function can set a maximum and minimum limit of the output frequency.
Even if a frequency command exceeds the maximum and minimum limiter
the inverter will ignore this value and stop at the values set.
Set first maximum limiter on setting.
Be sure that the maximum limiter (A061/A261) > minimum limiter (A062/A262).
The maximum and minimum limiter will not operate if 0Hz is set.
This function is not avalable under third control function.
Set item
Function
code
Setting limit
Contents
Frequency max.
limiter
A061/A261
0.00,
frequency min. limiter - max.
limiter
frequency
Unit : Hz
Setting max. of output
frequency
Frequency min. limiter A062/A262
0.00,
starting frequency - max. limiter
frequency
Unit : Hz
Setting min. of output
frequency
(1) In use O-L, OI-L case
(2) In use O2-L case
A061/A261:1
st
/ 2
nd
frequency maximum limiter
A062/A262: 1
st
/ 2
nd
Forward
A062
A061
Max.
frequency
A
/
Max. frequency
A004/A204/A304
A062
A061
10V
-10V
Reverse
Output frequency (Hz)
Max. frequency
A004/A204/A304
Frequency command
0V
4mA
10V
20mA
A062
A061
When frequency command is control
terminal (Terminal), by setting Min. limiter,
even if 0V is input, it is
not possible to
output less than the frequency set with Min.
limiter
Содержание V3000-015LF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...