Explanation of Function
Seite 93 / 180
Overload restriction
(1) Overload restriction
The Inverter monitors the motor current on acceleration and constant
speed, When the inverter reaches the overload restriction level, the
Inverter will reduce the output frequency automatically to restrict the
overload.This function prevents an over-current trip by inertia during
acceleration or radical changes in load at constant speed.
Two kinds of overload restriction function are set with b021, b022, b023
and b024, b025, b026. To change b021, b022, b023 and b024, b025,
b026, assign 39(OLR) to an intelligent input terminal. The current
value this function operates at is set in overload restriction level.
The overload restriction constant is the time to decelerate to 0Hz from
max frequency.
b021, b022, b023 and b024, b025, b026 is changed with OLR.
As this function operates, the acceleration time is longer than setting time.
If the overload restriction constant is set too short, in spite of accelerating, an over-voltage trip is caused with
regenerative enegy from the motor on automatic deceleration by this function.
When this function operates in the midst of accelerating, the frequency will not reach the goal frequency, the
Inverter will adjust in the following way.
Make acceleration time longer.
Raise torque boost.
Raise overload restriction level.
Set item
Function
code
Data Description
00 Invalid
01
Acceleration/valid on constant speed.
02
Valid on constant speed.
03
Acceleration/valid on constant speed. (Note 1)
Overload
restriction
Selection.
b021/b024
04
Valid on constant speed. (Note 1)
Overload
restriction Level.
b022/b025
Rated current x 0.5 to
Rated current x 2.0
Units :A
Current value overload restriction operates.
Overload
restriction
Constant.
b023/b026
0.1 to 30.0
Units :second
Deceleration time when overload restriction
Operates.
(Note 1): (Increase speed mode at the time of regenerating)
Overload restriction level
b022/b025
Output
Deceleration set with
overload restriction constant
Maximum frequency
A004/A204/A304
b021:Overload restriction selection
b022:Overload restriction level
b023:Overload restriction constant
b024:Overload restriction 2 selection
b025:Overload restriction level2
b026:Overload restriction constant2
C001-C008:Intelligent input
C021-C025:Intelligent output
C026:Alarm relay output setting
C040:Overload advance notice signal
t t
d
Relation code
Содержание V3000-015LF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...