Explanation of Function
Seite 94 / 180
(2) Overload advance notice
When the load is high, it is possible to adjust the load again by outputting an overload advance notice.
It is used to prevent damage to the machine from too much load, i.e. baggage on a conveyor, the Inverter
overload protection will operate.
Assign 03(OL) or 26(OL2) to an intelligent output terminal 11 - 15 or the alarm relay output terminal.
(Two kinds of overload advance notice signals are possible output.)
Set item
Function
code
Data Description
00
On acceleration, constant speed, this is
valid.
Overload
advance notice
signal output
mode selection
C040
01
On constant speed only, this is valid.
Overload
advance notice
level
C041
0.0
0.1 to
Rated current x
2
Don’t operate.
Units: A
As load reaches overload advance notice
level,
OL signal is output.
Overload
advance notice
level
C111
0.0
0.1 to
Rated current x
2
Don’t operate.
Units: A
As load reaches overload advance notice
level,
OL2 signal is output.
Inverter output
f
Overload advance notice level
C040
Output
OL/OL2
Goal frequency
F001
b023/b026
Overload restriction level
b022/b025
Содержание V3000-015LF
Страница 1: ...INVERTER Series V3000 M A N U A L...
Страница 13: ...General Descriptions Seite 13 180 6 2 Dimension 178...
Страница 91: ...Explanation of Function Seite 91 180 Reduced rated ratio Inverter output Frequency X1 0 0 60 X0 9 X0 8 5 2 5...
Страница 173: ...Explanation of Function Seite 173 180 RB N No conduct N RB No conduct...
Страница 179: ...Specification Seite 179 180 V3000 150 220NF HF V3000 300NF HF 2 31 26 54 51 10 19 25 22 2 39 37 7 22 9 24 19 92...
Страница 180: ...Specification Seite 180 180 V3000 370 450NF HF V3000 550NF HF 25 55 52 10 39 30 2 25 70 67 12 48 38 2...