Status word
1
Global error flag (1 = error)
2
Fieldbus control (1 = enabled)
3
Guard (Guard enabled models only) (1=guard open)
4
Over current error
5
Under voltage error
6
Over voltage error
7
Over temperature error
8
Motor stalled
9
Tacho fault
10
Leak detected
11
Low setpoint - out of range
12
High setpoint - out of range
13
Reserved
14
Reserved
15
Reserved
Device Related Diagnostic Data
Byte 1, 2, 3, 4, 5, 6*
Mandatory Slave Bytes
8 bit
Byte 7
Header byte
8 bit
Byte 8
Pump model
8 bit
Byte 9
Pump head
8 bit
Byte 10
Tube size (high byte)
8 bit
Byte 11
Tube size (low byte)
8 bit
Byte 12
Min speed (high byte)
8 bit
Byte 13
Min speed (low byte)
8 bit
Byte 14
Max speed (high byte)
8 bit
Byte 15
Max speed (low byte)
32 bit
Byte 16, 17, 18, 19
Software version, Main CPU
32 bit
Byte 20, 21, 22, 23
Software version, HMI CPU
32 bit
Byte 24, 25, 26, 27
Software version, Flash
32 bit
Byte 28, 29, 30, 31
Software version, PROFIBUS CPU
46
m-630un-en-08
Содержание 630 U
Страница 21: ...1 2 m 630un en 08 21 ...
Страница 62: ...14 7 Network topology Star network Ring network 62 m 630un en 08 ...
Страница 126: ...23 5 Flow Sensor Reading The flow sensor value can be read via the Flow sensor reading screen 126 m 630un en 08 ...
Страница 128: ...Press SELECT to choose an option Press EXIT to return to the screen from where the MENU was called 128 m 630un en 08 ...
Страница 158: ...Press HOME to return and store the setting The input is now enabled in manual mode 158 m 630un en 08 ...
Страница 159: ...25 Help 25 1 Help Select Help from the main menu to access the help screens m 630un en 08 159 ...
Страница 179: ...Number Spare Description 8 TT0005 10mm 3 8in spanner 9 MRA3026A Track assembly m 630un en 08 179 ...