Watlow PM PLUS™ 6
• 73 •
Chapter 6: Profiles
Profile Step Types
Step
Types
Description
Parameters in Step Type
Unused
Step
This is an empty step that can be used to plan for future steps to be inserted or
temporarily deactivate a step in a profile.
- - - -
Soak
A Soak Step maintains the last Target Set Points for the designated time. The
state of up to 2 event outputs may be set or maintained.
Hours
Minutes
Seconds
Event 1
Event 2
Wait For
Event
A Wait for Event Step waits for the two Wait for Event states (1 to 2) to match
the specified state. The state of up to 2 event outputs may be set or main-
tained.
Wait Event 1
Wait Event 2
Event 1
Event 2
Wait For
Process
A Wait for Process Step will wait for Process Value 1 or 2 to match the Wait
for Process Value. The state of up to 2 event outputs may be set or maintained.
Event 1
Event 2
Wait For
Both
A Wait For Process and Event Step will wait for Process Value 1 or 2 to match
the Wait for Process 1 value, and/or the two Wait Event states to match the
specified state. The state of up to 2 event outputs may be set or maintained.
Wait Event 1
Wait Event 2
Event 1
Event 2
Jump
A Jump step will repeat previous steps a number of times designated in Jump
Count. Jumps can be nested up to four deep. The state of up to 2 event out-
puts may be set or maintained.
Jump Step
Jump Count
Event 1
Event 2
End
An End Step will end the profile and set the control modes and set points to
match the End Type. The state of up to 2 event outputs may be set or main-
tained. The event outputs will not be set off unless specifically stated in this
step. If a profile does not have an End Step, the profile continues until step 40,
then stops and maintains the last set points and control modes.
End Type
Event 1
Event 2
Time
If Ramping Type in Setup - Global is set for Time, the control loop will follow
set point over the specified time. If two loops of control are present then they
will both follow independent set points over the specified time. The state of up
to 2 event outputs may be set or maintained.
Target Set Point Loop 1
Target Set Point Loop 2
Hours
Minutes
Seconds
Event 1
Event 2
Ramp
Rate
If Ramping Type found in the Global Menu of the Setup Page is set for Rate,
specify the rate of change in degrees or units per minute. The state of up to 2
event outputs may be set or maintained.
Target Set Point Loop 1
Target Set Point Loop 2
Rate
Event 1
Event 2