Chapter 4: Operations
Chapter 4: Operations
All parameters and lists of options are accessed via the
Operations
List.
Parameters directly in the Operations List are generally used for operations and monitoring. (Additional
parameters are located in the Setup, Factory, Profile, and Global Lists, which you can access via
Operations
). The Operations List includes:
• Default parameters/sublists that vary depending on the features enabled on your device, as indicated on
the configuration code.
• Custom parameters that you have added via
Operations — Factory — Custom Setup
(See "Adding
Custom Parameters to the Operations List.")
• Setup List
• Profile Status and Profile Lists (if enabled on your device)
• Factory List
If you choose to use Modbus
®
or another communication protocol to write to the PM PLUS, you will need
the parameter IDs. For details about fieldbus addresses and Data Types, refer to the "EZ-ZONE All Register
List."
Operations List
Default Operations Parameters/Sublists
The default parameters in the Operations List vary on every PM PLUS. This list is populated with
parameters applicable to the features enabled on the device and the settings chosen in
Operations
— Setup
. (Refer to the configuration code on the device's product label).
Parameter
Description
Range
Default
ID
Control Mode
Active
View the current control mode.
Off (62)
Auto (10)
Manual (54)
- - - -
8002
Heat Power
View the current heat output level.
0.0 to 100.0%
- - - -
8011
Cool Power
View the current cool output level.
-100.0 to 0.0%
- - - -
8014
Autotune
Start an autotune. While active, "Autotune"
displays on the Home Screen.
Yes (106)
No (59)
No
8026
Timer Functions
These appear in the Operations List on devices with T in the 4th digit, for timer enabled models
Ready Band State Display whether the process value is in the
ready band.
Yes (106)
No (59)
- - - -
31022
Ready Band
Set how close the process value must be to
the closed loop timer set point to be in the
ready band.
0.000 to 9999.000°F or units
0.000 to 5555.000°C
5
31023
Closed Loop
Timer Set Point
The set point that will be in effect during
the timer period
-1999.000 to 9999.000°F or units
-1110.555 to 5555.000°C
75
31028
Hours
Set the timer period hours.
0 to 99
0
31025
Minutes
Set the timer period minutes.
0 to 59
0
31026