Watlow PM PLUS™ 6
• 116 •
Chapter 10 Appendix
Reversed
Range limiting only
RTD
S1 open
Yes, pulled up.
S2 open
Not implemented.
S3 open
Yes, pulled up.
S1 short to S2
Yes, pulled up
S1 short to S3
Yes, pulled down to under range.
S2 shorted to S3
Not implemented, Possible, monitor S2 voltage.
S1 and S2 open
Yes, pulled down to under range.
S1 and S3 open
Yes, S1 pulled up.
S2 and S3 open
Yes pulled up.
Thermistor
S1 open
Yes, pulled up to sensor over range.
S3 open
Yes, pulled up to sensor over range.
S1 short to S3
Yes, pulled down to sensor under range.
S1 and S3 open
Yes, S1 pulled up to sensor over range.
Содержание PM PLUS 6