Watlow PM PLUS™ 6
• 65 •
Chapter 5: Setup
Setup Lists
You will not see every parameter listed here. These vary depending on the features enabled on your device.
CIP Target2Orig Qty
CIP Implicity Assembly Output Member Quantity 1 to 20
40
24009
CIP Orig2Target Qty
CIP Implicity Assembly Input Member Quantity 1 to 20
40
24010
Display Units
Select which scale to use for temperature
passed over communications port 2.
°F (30)
°C (15)
°F
17050
Non-volatile Save
If set to Yes all values written to the control
will be saved in EEPROM. The EEPROM allows
for approximately one million writes.
Yes (106)
No (59)
No
17051
Operations — Setup — Digital Bus (J1939 CAN) —
J1939 Node Address
Set the Device address.
0 to 255
249
94001
J1939 Baud Rate
Set the Digital Input Bus communications
speed.
125 kb (1351)
250 kb (1352)
500 kb (1353)
1000 kb (1364)
250
94002
J1939 Device Enable
Enables the device for communication.
No (59)
Yes (106)
Yes
94003
TEDS Read Enable
Transducer Electronic Data Sheet. Contains
sensor technical characteristics when manu-
factured.
No (59)
Yes (106)
Yes
94004
Display Units
Select which scale to use for temperature
passed over communications port 2.
°C (15)
°F (30)
None (61)
°C
17050
Data Map
If set to 1 the control will use legacy Modbus
®
mapping. If set to 2, the control will use new
Modbus
®
mapping to accommodate new func-
tions. Not used with J1939.
1 to 2
1
17059
Non-volatile Save
If set to Yes all values written to the control
will be saved in EEPROM. The EEPROM allows
for approximately one million writes.
Yes (106)
No (59)
No
- - - -
Operations — Setup — Profibus DP —
Profibus Address
Set the Profibus address for this control.
0 to 126
126
17060
Address Lock
When set to yes will not allow address to be
changed using software. Can be changed from
front panel.
No (59)
Yes (106)
No
17061
Status
Profibus DP Status
Current Profibus status.
Ready (1662)
Running (149)
- - - -
17062
Display Units
Select which scale to use for temperature
passed over communications port 2.
°F (30)
°C (15)
°F
17050
Non-volatile Save
If set to Yes all values written to the control
will be saved in EEPROM. The EEPROM allows
for approximately one million writes.
Yes (106)
No (59)
No
17051
Operations — Setup — Modbus
®
TCP or EtherNet/IP —
Modbus
®
Word Order Select the word order of the two 16-bit words
in the floating-point values.
Low-High (1331)
High-Low (1330)
Low-High
17043
IP Address Mode
Select DHCP to let a DHCP server assign an
address to this module.
DHCP (1281)
Fixed Address (1284)
DHCP
17012
Note: When changing IP address, the control power must be cycled for the new address to take effect.